![](img/compere_shop_all.png) - Show All ![](img/compere_shop_identical.png) - Show differences - Back | ![](img/eclose_grey.png) POE SWITCH WITH BUFFERED POWER SUPPLY IPUPS-9-11-F 9-PORT ATTE | ![](img/eclose_grey.png) MULTIFUNCTION METER FOR ELECTRICAL INSTALLATIONS UT-595 UNI-T |
| ![IPUPS-9-11-F Click on the picture to see a detailed description](https://sklep.delta.poznan.pl/shop_image/product/ipups-9-11-f_m.jpg) | ![UT-595 Click on the picture to see a detailed description](https://sklep.delta.poznan.pl/shop_image/product/ut-595_m.jpg) |
| 232.92 EUR 232.92 EUR
| 570.16 EUR 570.16 EUR
|
LAN ports: | 1 x RJ45 10/100 Base-T - Uplink, 9 x RJ45 10/100 Base-T + PoE (802.3af/at) / Passive PoE | ... |
Management: | | ... |
Resistance measurement: | ... | Test voltage 250 V : 0.05 MΩ ... 250 MΩ Test voltage 500 V : 0.05 MΩ ... 500 MΩ Test voltage 1000 V : 0.05 MΩ ... 1000 MΩ |
LED diodes: | AC, DC, CHARGING (battery charging), PoE | ... |
Measuring accuracy: | ... | 0.05 MΩ ... 1000 MΩ ± (5% + 5) |
Open circuit voltage: | ... | Test voltage ± 10 % |
Transmission speed: | 10 / 100 Mbps : 1 x Port Uplink, 10 / 100 Mbps : 9 x Port LAN & PoE | ... |
Test current: | ... | 0.9 mA ... 1.1 mA |
Short-circuit current: | ... | < 1.8 mA |
AC voltage measurement: | ... | 0 V ... 440 V ± (2% + 3) @ 1 V |
Maximal output power: | 40 W @ Passive PoE - LAN1 ... LAN4 ports, 60 W @ Passive PoE - Port LAN5, 30 W @ PoE (802.3af/at) - LAN1 ... LAN5 ports | ... |
DC voltage measurement: | ... | 0 V ... ± 440 V ± (2% + 3) @ 1 V |
Maximal total power: | 60 W | ... |
Measurement of small resistances: | ... | 0.01 Ω ... 200 Ω ± (2% + 5) |
Frequency measurement: | ... | 20 Hz ... 100 Hz - for reference only |
Operation modes: | Standard : 100 m @ 10/100 Mb/s - LAN1 ... LAN6 ports Long Range : 280 m @ 10 Mb/s - LAN1 ... LAN4 ports ; 100 m @ 10/100 Mb/s - LAN5, LAN6 ports | ... |
Test of RCDs: | ... | Working voltage: 220V ± 10 % Test current: 10mA / 30mA / 100mA / 300mA / 500mA Switch-off time ranges :
- 0 ... 2000 ms ± (5% + 5) @ 1/2 x nominal value of the residual current
- 0 ... 500 ms ± (5% + 5) @ 1 x nominal value of the residual current, Selective RCD
- 0 ... 500 ms ± (5% + 5) @ 2 x nominal value of the residual current, Selective RCD
- 0 ... 300 ms ± (5% + 5) @ 1 x nominal value of the residual current
- 0 ... 300 ms ± (5% + 5) @ 2 x nominal value of the residual current
- 0 ... 40 ms ± (5% + 5) @ 5 x nominal value of the residual current
|
RCD tripping current measurement: | ... | Increasing current test: 10 mA / 30 mA / 100 mA / 300 mA / 500 mA ± 10 % |
RCD automatic test: | ... | |
Phase sequence test: | ... | 100 V ... 440 V / 45 Hz ... 65 Hz |
Continuity measurement of protective and equalizing conductors: | ... | 0 Ω ... 199 Ω ± (2% + 5) Measuring current > 20 mA @ 0 ... 2 Ω |
Line impedance measurement (L-N): | ... | 0.05 Ω ... 1.99 Ω ± (5% + 5) 2 Ω ... 19.99 Ω ± (5% + 5) 20 Ω ... 2000 Ω ± (5% + 5) Measuring current : 20 A / 20 ms Measuring range of prospective short-circuit current : 0 ... 26 kA |
Short circuit loop impedance measurement (L-PE): | ... | 0.05 Ω ... 1.99 Ω ± (5% + 5) 2 Ω ... 19.99 Ω ± (5% + 5) 20 Ω ... 2000 Ω ± (5% + 5) Measuring current : 20 A / 20 ms Measuring range of prospective short-circuit current : 0 ... 26 kA |
Automatic change of measuring ranges: | ... | |
RS-232: | ... | |
USB: | ... | |
Main features: | The ability to independently turn on and off the PoE power for each of the LAN 1 ... LAN 9 ports The modular design streamlines service tasks and enables quick and easy system expansion The raster system of module assembly facilitates the expansion of the device by further modules Place for battery : 12 V / 18 Ah Battery charging current : 1 A / 2 A - (set with the JP1 jumper) Battery - Protection against reverse polarity connection, Protection against deep discharge of the battery Technical outputs of the OC type signaling loss of voltage at the PSU output (OUF) and loss of voltage in the 230V mains (ACF) PSU thermal protection : 130 °C Overload protection LAN & PoE ports - Short-circuit protection, Overvoltage TAMPER switch indicating open the cover "Index of Protection" : IP20 | Warning of using high voltage during the measurement, Phase switch 0° / 180° during RCD test, Automatic identification of AC/DC voltage, Reset function for measuring low resistances, Large, readable LCD display with backlight, Buzzer, Automatic power-off, Low battery indicator, Aesthetic and solid construction |
Operation temp: | ... | 0 °C ... 40 °C |
Permissible relative humidity: | ... | ≤ 85 % (non-condensing) |
Power supply: | 190 ... 260 V AC | 8 x 1.5V, type AA/LR6/FR6 battery - included |
Weight: | 2.48 kg | 1.1 kg |
Dimensions: | 325 x 305 x 100 mm | 210 x 175 x 90 mm |
Manufacturer / Brand: | ATTE | UNI-T |