![](img/compere_shop_all.png) - Show All ![](img/compere_shop_identical.png) - Show differences - Back | ![](img/eclose_grey.png) INSULATION RESISTANCE METER + RCD TESTER UT-526 UNI-T | ![](img/eclose_grey.png) AHD, HD-CVI, HD-TVI, PAL CAMERA DS-2CE16H8T-IT3F(2.8mm) - 5 Mpx Hikvision |
| ![UT-526 Click on the picture to see a detailed description](https://sklep.delta.poznan.pl/shop_image/product/ut-526_m.jpg) | ![DS-2CE16H8T-IT3F(2.8mm) Click on the picture to see a detailed description](https://sklep.delta.poznan.pl/shop_image/product/ds-2ce16h8t-it3f_m.jpg) |
| 211.00 EUR 211.00 EUR
| 115.92 EUR 115.92 EUR
|
Resistance measurement: | Test voltage 250 V : 0.05 MΩ ... 200 MΩ Test voltage 500 V : 0.05 MΩ ... 300 MΩ Test voltage 1000 V : 0.05 MΩ ... 500 MΩ |
Measuring accuracy: | 0.05 MΩ ... 500 MΩ ± (5% + 5) |
Open circuit voltage: | Test voltage + 10 % |
Test current: | 0.9 mA ... 1.1 mA |
Short-circuit current: | < 1.8 mA |
AC voltage measurement: | 0 V ... 440 V ± (2% + 3) @ 1 V |
DC voltage measurement: | 0 V ... 440 V ± (2% + 3) @ 1 V |
Measurement of small resistances: | 0.01 Ω ... 2000 Ω ± (2% + 5) |
Frequency measurement: | 20 Hz ... 100 Hz - for reference only |
Test of RCDs: | Working voltage: 220V ± 10 % Test current: 10mA / 30mA / 100mA / 300mA Switch-off time ranges :
- 0 ... 2000 ms ± (5% + 2) @ 10 mA
- 0 ... 500 ms ± (5% + 2) @ 30 mA
- 0 ... 300 ms ± (5% + 2) @ 100 mA
- 0 ... 300 ms ± (5% + 2) @ 300 mA
|
Automatic change of measuring ranges: |
|
RS-232: | |
USB: | |
Main features: | Warning of using high voltage during the measurement, Phase switch 0° / 180° during RCD test, Automatic identification of AC/DC voltage, Large, readable LCD display with backlight, Buzzer, Low battery level alarm, Aesthetic and solid construction |
Operation temp: | 0 °C ... 40 °C |
Permissible relative humidity: | ≤ 85 % (non-condensing) |
Power supply: | 6 x 1.5V, type AA/LR6/FR6 battery - included |
Weight: | 0.45 kg |
Dimensions: | 150 x 100 x 71 mm |
Manufacturer / Brand: | UNI-T |
Guarantee: | 2 years |