- Show All - Show differences - Back | VIDEO BALUN TR-8H/DC/R10 | MULTIFUNCTION METER FOR ELECTRICAL INSTALLATIONS UT-593 UNI-T |
| | |
| 53.57 EUR 53.57 EUR
| 458.27 EUR 458.27 EUR
|
Standard: | AHD - 5 Mpx, HD-CVI - 8 Mpx 4K UHD, HD-TVI - 8 Mpx 4K UHD, CVBS - PAL, NTSC | ... |
Input current: | 2 x max. 10 A | ... |
Resistance measurement: | ... | Test voltage 250 V : 0.05 MΩ ... 250 MΩ Test voltage 500 V : 0.05 MΩ ... 500 MΩ Test voltage 1000 V : 0.05 MΩ ... 1000 MΩ |
Maximal power voltage: | max. 40 V DC / 28 V AC | ... |
Max. output current for single output: | 2.5 A | ... |
Device type: | Passive | ... |
Measuring accuracy: | ... | 0.05 MΩ ... 1000 MΩ ± (5% + 5) |
Number of channels: | 8 Video + DC | ... |
Open circuit voltage: | ... | Test voltage ± 10 % |
Coaxial socket voltage range 75Ω (CVBS): | 1 Vpp | ... |
Test current: | ... | 0.9 mA ... 1.1 mA |
Short-circuit current: | ... | < 1.8 mA |
AC voltage measurement: | ... | 0 V ... 440 V ± (2% + 3) @ 1 V |
Video transmission range: | 250 m @ 720p - UTP cat. 5e 400 m @ CVBS - PAL / NTSC - UTP cat. 5e | ... |
DC voltage measurement: | ... | 0 V ... ± 440 V ± (2% + 3) @ 1 V |
Measurement of small resistances: | ... | 0.01 Ω ... 200 Ω ± (2% + 5) |
Frequency measurement: | ... | 20 Hz ... 100 Hz - for reference only |
Attenuation: | 4.43 MHz @ 0.09 dB 11 MHz @ 0.42 dB 21 MHz @ 1.04 dB 38 MHz @ 0.85 dB 42 MHz @ 1.00 dB 67.5 MHz @ 0.87 dB | ... |
Coaxial socket impedance: | 75 Ω | ... |
Symmetrical socket impedance: | 100 Ω | ... |
Connectors type: | Video - 8 x BNC Socket DC - Cable terminals | ... |
Symmetrical socket type: | Cable terminals | ... |
Housing type: | Rack 10", 1U | ... |
Test of RCDs: | ... | Working voltage: 220V ± 10 % Test current: 10mA / 30mA / 100mA / 300mA / 500mA Switch-off time ranges :
- 0 ... 2000 ms ± (5% + 5) @ 1/2 x nominal value of the residual current
- 0 ... 500 ms ± (5% + 5) @ 1 x nominal value of the residual current, Selective RCD
- 0 ... 300 ms ± (5% + 5) @ 1 x nominal value of the residual current
- 0 ... 40 ms ± (5% + 5) @ 5 x nominal value of the residual current
|
RCD tripping current measurement: | ... | Increasing current test: 10 mA / 30 mA / 100 mA / 300 mA / 500 mA ± 10 % |
RCD automatic test: | ... | |
Phase sequence test: | ... | 100 V ... 440 V / 45 Hz ... 65 Hz |
Continuity measurement of protective and equalizing conductors: | ... | 0 Ω ... 199 Ω ± (2% + 5) Measuring current > 20 mA @ 0 ... 2 Ω |
Line impedance measurement (L-N): | ... | 0.05 Ω ... 1.99 Ω ± (5% + 5) 2 Ω ... 19.99 Ω ± (5% + 5) 20 Ω ... 2000 Ω ± (5% + 5) Measuring current : 20 A / 20 ms Measuring range of prospective short-circuit current : 0 ... 26 kA |
Power supply distance: | Power supply 12V DC
353 m @ 50 mA 235 m @ 75 mA 176 m @ 100 mA 141 m @ 125 mA 117 m @ 150 mA 88 m @ 200 mA 70 m @ 250 mA 58 m @ 300 mA 50 m @ 350 mA 44 m @ 400 mA 39 m @ 450 mA 35 m @ 500 mA 29 m @ 600 mA 25 m @ 700 mA 22 m @ 800 mA 19 m @ 900 mA 17 m @ 1000 mA | ... |
Short circuit loop impedance measurement (L-PE): | ... | 0.05 Ω ... 1.99 Ω ± (5% + 5) 2 Ω ... 19.99 Ω ± (5% + 5) 20 Ω ... 2000 Ω ± (5% + 5) Measuring current : 20 A / 20 ms Measuring range of prospective short-circuit current : 0 ... 26 kA |
Automatic change of measuring ranges: | ... | |
RS-232: | ... | |
USB: | ... | |
Main features: | ... | Warning of using high voltage during the measurement, Phase switch 0° / 180° during RCD test, Automatic identification of AC/DC voltage, Reset function for measuring low resistances, Large, readable LCD display with backlight, Buzzer, Automatic power-off, Low battery indicator, Aesthetic and solid construction |
Operation temp: | -10 °C ... 55 °C | 0 °C ... 40 °C |
Permissible relative humidity: | < 95 % | ≤ 85 % (non-condensing) |
Power supply: | ... | 8 x 1.5V, type AA/LR6/FR6 battery - included |
Weight: | 0.28 kg | 1.1 kg |
Dimensions: | 256 x 44 x 53 mm | 210 x 175 x 90 mm |
Manufacturer / Brand: | DELTA | UNI-T |
Guarantee: | 3 years | 2 years |